THREE PHASE PROTECTIVE RELAY TEST SET
-
-
Large Image :
THREE PHASE PROTECTIVE RELAY TEST SET
|
Product Details:
Place of Origin: |
Beijing, China |
Brand Name: |
GFUVE |
Certification: |
ISO 9001 : 2008; CE |
Model Number: |
TEST-330B |
Payment & Shipping Terms:
Minimum Order Quantity: |
1SET |
Price: |
USD20000-35000 |
Packaging Details: |
Standard export box |
Delivery Time: |
whitin 20 days |
Payment Terms: |
T/T, Western Union, Paypal |
Supply Ability: |
200pcs/month |
|
Detailed Product Description
CLASS: |
0.1, 0.2 |
TYPE: |
PROTECTIVE RELAY TEST SET |
TEST-330B THREE PHASE PROTECTIVE RELAY TEST SET
Test-330B three phase protective relay test set is a three phase current output and five phase voltage output relay tester with embedded host machine equipped with Complex Programmable Logic Device.
FEATURES
-
Three phase current output
-
Five phase voltage output
-
Accuracy class 0.2%
-
Embedded host machine equipped with Complex Programmable Logic Device (CPLD)
-
Eight-path synchronous D/A output in a single machine
-
High-accuracy linear power amplifier
-
Host machine integrated single cabinet structure with big LCD screen and complete interface has obtained appearance patent
-
Intelligent self-protection function
-
Plentiful Binary and powerful software function
-
Easily complete the ABB, Siemens, AREVA, Schneider, GE, SEL, VAMP, Toshiba, NR, Sifang and other foreign manufacturers of protective device test
-
Synchronous output of five-phase voltage and three-phase current, Max AC current output is 90A, Max AC voltage output is 260V
OVERVIEW
-
Three phase current output
-
Five phase voltage output
-
Accuracy class 0.2%
TEST ITEM
-
U/I test
-
DC test
-
Impedance characteristics
-
Power direction test
-
I-T test
-
Differential relay
-
Harmonic test
-
Differential protection
-
Distance protection
-
Zero sequence protection
-
Setting group test
-
State sequence
-
Synchronization test
-
Special test
-
Oscillation test
-
Metering instrument
-
Hardware checkout
-
Low Voltage protection
PARAMETERS
Electrical parameters |
Power voltage |
AC220V±10% or AC110V±10%, 50/60Hz±10% |
Time measurement |
0.1ms-999999.999s |
AC current output |
Phase current output (effective value) |
3 x 0-30A |
Maximum power output |
260VA/phase |
Maximum parallel current output (effective value) |
0-90A |
Long-term allowable working value of phase current
(effective value) |
>10A |
Allowable working time of maximum current |
>11s |
Accuracy class |
<±0.2% |
AC voltage output |
Phase voltage output (effective value) |
5 x 0-130V |
Line voltage output (effective value) |
0-260V |
Maximum power output |
70VA/phase |
Accuracy class |
<±0.2% |
DC current output |
Output range |
-10 to 10A or 3 x 0 to ±10A |
Maximum power output |
200VA |
Accuracy class |
<±0.2% |
DC voltage output |
Output range |
0-300V or 5 x 0 to ±130V |
Maximum output power |
130VA |
Accuracy class |
<±0.2% |
Binary input |
Idle contact |
1-20mA, 24V (DC) |
Electric potential contact |
250V/0.5A (DC) |
Binary output |
Idle contact |
250V/0.5A (DC) |
Rated output |
Frequency error |
<±0.01Hz |
Phase error |
<±0.2° |
Waveform distortion |
<±0.3% (fundamental wave) |
Time error |
<40µs |
Output frequency |
0-1050Hz |
Superposed harmonic wave |
0-21times |
Mechanical parameters |
Dimensions (L×W×H) (mm) |
360x195x375 |
Weight (kg) |
16.6 |
Environmental conditions |
Use range |
0°C to 45°C |
Storage range |
-25°C to 70°C |