Usage: | Magnetic Sensor | Theory: | Current Sensor |
---|---|---|---|
Output: | Analog Sensor | HQ46: | CLAMP ON CURRENT SENSORS |
Class: | 0.1 | Ratio: | 500A/500mA |
Color: | Black | Weight: | 500g |
The HQ46 AC Current Probe is designed for easy installed in tight spaces and without the need for dismantling the primary busbar or cables. The sensing head uses sliding push-fit clamp structure, safety isolation to avoid the user to contact with charged objects directly. It complies with CE standards and meets 600V CAT III safety class.
Electrical parameters | |
---|---|
Rated primary current | 500A AC |
Output voltage | 1 mV AC/A |
Amplitude accuracy | ±0.3%RD±0.02%FS (10%~100%I1n), 45Hz- 66Hz|Wire centered |
Phase accuracyt | ±0.5°(10%~100%I1n) (45Hz-5kHZ) |
The amplitude frequency characteristic | ±1% (45Hz-5kHZ) (Deviation accuracy) |
Conductor impact | ±0.5% (Off-center) |
The influence of external lector magnetic fields | ≤0.1A (In AC 400A/m electromagnetic fields) |
Maximum input current | 550A AC (Continuous) (45-66Hz, Ambient temperature 50°C) |
Temperature coefficient | ±0.02%/°C of the reading data |
Dielectric strength | 5500 V AC rms/Continue 15 seconds (Circuits-iron core, iron core-shell) |
The maximum rated voltage | 600V AC rms |
Applicable standards | Safety: EN61010-2-032:2002,300V CAT III, Contamination II EMC: EN61326:1997+A1:1998+A2:2001+A3:2003(Class A) |
Mechanical parameters | |
Measurable conductor diameter | Max.46mm |
Cable length | About 3 m |
Dimension (W x H x E) | About 96×160×40 (Excluding protruding parts) |
Weight | About 395g |
Environmental conditions | |
Operating temperature | 0 to 50°C (32-122°F) |
Operating humidity | ≤80%RH(No condensate) |
Storage temperature | -10 to 60°C (14-140°F) |
Storage humidity | ≤80%RH(No condensate) |
Operating environment | Indoor, altitude up to 2000 meters |